beautypg.com

Digital inputs, Digital inputs 35, Figure 2.22—wiring digital inputs 35 – Watlow Series D8 User Manual

Page 53

background image

Series D8 User’s Guide

Chapter 2: Installation

Doc. 0600-3120-2000

Watlow Anafaze

35

Digital Inputs

All digital inputs are transistor-transistor logic (TTL) level in-

puts referenced to controller common and the internal +5 V

power supply of the D8.
When an input is connected to the controller common, the in-

put is considered on. Otherwise, the input is considered off.

Most features that use the digital inputs can be user-config-

ured to activate when an input is either on or off.
In the off state, internal 4.7 k

resistors pull the digital inputs

high to 5 Vdc with respect to the controller common.

Table 2.5

Digital Input States and Values
Stored in the Controller

1

Read and write these values through communications.

External Switching Device

To ensure that the inputs are reliably switched, use a switching

device with the appropriate impedances in the on and off

states and do not connect the inputs to external power sources.
When open, the switching device must provide an impedance

of at least 14 k

to ensure that the voltage will rise to greater

than 3.7 Vdc. When closed, the switch must provide not more

than 1.7 k

impedance to ensure the voltage drops below 1.3

Vdc.
To install a switch as a digital input, connect one lead to the

common terminal on the TB50 (terminals 3 and 4) or TB18

(terminal 2). Connect the other lead to the desired digital input

terminal on the TB50 (terminals 43 to 50) or TB18 (terminals

16 to 18).

Figure 2.22 Wiring Digital Inputs

State

Value

1

Description

Off

0

Open circuit

On

1

Digital input connected to controller

common

External

Switching

Device

TB50

Input

Control Com