161

alarm, turns on the global alarm output. The global alarm re-

mains on until the alarm is acknowledged. The message per-

sists until the condition is corrected and the alarm is

acknowledged.
The D8 displays the following system alarm messages:

Low power

: See Low Power on page 163.

Battery dead

: See Battery Dead on page 163.

H/W error: Ambient

: See H/W Error: Ambient on page

165.

H/W error: Gain

: H/W Error: Gain or Offset on page

164.

H/W error: Offset

: See H/W Error: Gain or Offset on

page 164.

Other Behaviors

Table 7.2 indicates potential problems with the system or con-

troller and recommends corrective actions.

Table 7.2

Other Symptoms

Symptom

Possible Causes

Recommended Action

Indicated tempera-

ture not as expected

Controller not communicating
Sensor wiring incorrect
Noise

See Checking Analog Inputs on page 166.

D8 display is not lit

Power connection incorrect

Check wiring and service. See Wiring the

Power Supply on page 23.

Failed flash memory chip

Replace the flash memory chip. See

Replacing the Flash Memory Chip on page

170.

D8 damaged or failed

Return the D8 for repair. See Returning a

Unit on page 158.

D8 display is lit, but

keys do not work

Keypad locked

See Keys Do Not Work on page 166.

Unacknowledged alarm

An alarm condition exists and has not been

acknowledged. See How to Acknowledge

an Alarm on page 82.

D8 damaged or failed

Return the D8 for repair. See Returning a

Unit on page 158.