Chapter 4: Operation and Setup

Series D8 User’s Guide

106

Watlow Anafaze

Doc. 0600-3120-2000

Figure 4.14 Application Using Ratio Control

Table 4.11

Ratio Control Settings for the Ratio
Loop (Loop 2) in the Example

Setting Up Differential Control

Differential control is a simple application of ratio control,

used to control one process (ratio loop) at a differential, or off-

set, to another process (master loop).

Menu

Parameter

Value

Comment

Ratio

Ratio master loop

01

Loop 1 is the master loop.

Ratio

Ratio low SP

0.0

The minimum ratio loop set point is 0.0 gallons

per second (gps).

Ratio

Ratio high SP

7.0

The maximum ratio loop set point is 7.0 gps.

Ratio

Control ratio

0.5

The H

2

0 flow rate (10 gps) is multiplied by 0.5

to obtain the KOH flow rate (5 gps).

Ratio

Ratio SP diff

0

For this example, there is no set point differen-

tial.

D8

Loop 1 PID Output

Loop 2 PID Output

Loop 1 Input

Process Variable

Loop 2 Input

Process Variable

Motorized Control Valve 2

Motorized

Control

Valve 1

Mixture Output

Water Input

KOH Input

Flow

Transducer

Loop 1: Water Flow Control Loop

Loop 2: KOH Flow Control Loop