Chapter 2: Installation

Series D8 User’s Guide

36

Watlow Anafaze

Doc. 0600-3120-2000

Functions Activated by Digital Inputs

Use digital inputs to activate the following functions:

Load a job that is stored in controller memory. See BCD

Job Load on page 126.

Change all loops to manual mode at specified output lev-

els. See Mode Override on page 127.

Enable thermocouple short detection. See Thermocouple

Short Alarm on page 129.

Restore automatic control after a failed sensor has been

repaired. See Restore Automatic Mode on page 138.

TB18 Connections

Table 2.6

TB18 Connections

1

The indicated outputs are dedicated for control when enabled in the

loop setup. If one or both of the outputs are disabled for a loop, then the
corresponding digital outputs become available for alarms.

2

If you install a Watlow Anafaze Serial DAC, the D8 series controller

uses digital output 18 (terminal 15) for a clock line. You cannot use out-
put 18 for anything else if a Serial DAC is installed.

Control Output

1

Terminal

Function

D84 _ - _ _ _ _ - _ _ _ _

D88 _ - _ _ _ _ - _ _ _ _

1

+5 Vdc

2

CTRL COM

3

Watchdog timer

4

Global alarm

5

Output 1

Loop 1 heat

Loop 1 heat

6

Output 2

Loop 2 heat

Loop 2 heat

7

Output 3

Loop 3 heat

Loop 3 heat

8

Output 4

Loop 4 heat

Loop 4 heat

9

Output 5

Loop 1 cool

Loop 5 heat

10

Output 6

Loop 2 cool

Loop 6 heat

11

Output 7

Loop 3 cool

Loop 7 heat

12

Output 8

Loop 4 cool

Loop 8 heat

13

Output 9

Loop 1 cool

14

Output 10

Loop 2 cool

15

Output 18

2

Serial DAC clock

Serial DAC clock

16

Input 1

17

Input 2

18

Input 3