Alarm Function: Standard Alarm or Boost Output

You can configure each process alarm as either a standard

alarm or a boost alarm:

A standard alarm provides traditional alarm functional-

ity: The operator must acknowledge the alarm message

on the controller display, a latching global alarm is acti-

vated, and the alarm can activate a user-specified non-

latching alarm output.

A boost alarm provides on/off control output using the

alarm set points. For example, you could configure a

high deviation alarm to turn on a fan. The alarm activates

a user-specified non-latching output. Alarm messages do

not have to be acknowledged, and the global alarm is not

activated.

Alarm High and Alarm Low

An alarm high occurs if the process variable rises above a

user-specified value. An alarm low occurs if the process vari-

able drops below a separate user-specified value. See Figure

4.7
Enter the alarm high and low set points at the Alarm high SP

and Alarm low SP parameters in the Alarms menu.

Figure 4.7

Activation and Deactivation of
Process Alarms

Deviation Alarms

A deviation alarm occurs if the process deviates from set point

by more than a user-specified amount; see Figure 4.7. You can

Set point

Alarm high SP

Alarm low SP

}

Hysteresis

Alarm high on

Alarm high off

Alarm low on

Alarm low off

High deviation

alarm off

High deviation

alarm on

Low deviation

alarm off

Low deviation

alarm on

Set point + HiDeviation value

Set point - HiDeviation value

}

Hysteresis

}

Hysteresis

}

Hysteresis