beautypg.com

Assigning plc addresses, Assigning plc addresses 51, Figure 3.5—adding the d8 to the scanlist 51 – Watlow Series D8 User Manual

Page 69

background image

Series D8 User’s Guide

Chapter 3: Communicating by DeviceNet

Doc. 0600-3120-2000

Watlow Anafaze

51

device starting at the next available byte in the PLC

memory. When not checked the user controls how the

bytes are arranged.)

3. Select 01 Watlow D84/D88 by clicking it in the Available

Devices

list.

4. Click the right-arrow button to put the D8 on the Scanlist.

Figure 3.5

Adding the D8 to the Scanlist

Assigning PLC Addresses

Once the device has been added to the Scanlist, it is possible

to map the polled bytes to any available contiguous memory

location for both inputs and outputs.
The Allen-Bradley 1747-SDN scanner module in this exam-

ple consumes the first 32 words of the input and output files

corresponding to the slot in which it is inserted. For example,

when the module is inserted in slot 3 of the PLC, the scanner

uses addresses in the input file I:3.0 through I:3.31. This pro-

vides only 32 words of memory. Because the D88 controller

supplies 81 bytes or 40.5 words of input, it is necessary to map

the incoming polled data to the scanner's M1 file instead.
The following procedure maps the D88's input bytes to the

scanner's M1 file. Actually only 40 words or 80 bytes of input

data will be mapped because the Exception Status Byte, which

is currently unused, is excluded.