beautypg.com

Installing scaling resistors, Input circuit, Installing scaling resistors 172 – Watlow Series D8 User Manual

Page 190: Input circuit 172

background image

Chapter 7: Troubleshooting and Reconfiguring

Series D8 User’s Guide

172

Watlow Anafaze

Doc. 0600-3120-2000

Installing Scaling Resistors

Resistors are installed for all inputs on the D8. Inputs with sig-

nal ranges between -10 and +60 mV use 0

resistors in the

RC position only. All other input signals require special input

scaling resistors.

CAUTION!

Scaling resistors are soldered to the circuit
board. Only qualified technicians should at-
tempt to install or remove these components.
Improper techniques, tools or materials can
result in damage to the controller that is not
covered by the warranty.

Input Circuit

The D8 can accept thermocouple, mVdc, Vdc, mAdc and

RTD inputs. Unless ordered with special inputs these control-

ler accept only signals within the standard range -10 to 60

mVdc.
To accommodate other signals, the input circuit must be mod-

ified. When configured for thermocouple inputs, 0

resistors

are installed in all RC locations. To accommodate voltage sig-

nals outside the standard range, milliamp current signals or

RTDs, resistors are added or replaced to scale the signals to

the standard range. These resistor can be installed by Watlow

Anafaze or by a qualified electronics technician using scaling

resistors supplied by Watlow Anafaze.
Figure 7.4 shows the input circuit for one differential analog

input. See Current Inputs on page 173 through RTD Inputs on

page 175 for specific instructions and resistor values for volt-

age, current and RTD inputs.

NOTE!

When adding your own scaling resistors to
the controller, for voltage and RTD inputs
you will have to carefully remove one of the
RC resistors in order to install the resistor