beautypg.com

Watlow Series D8 User Manual

Page 51

background image

Series D8 User’s Guide

Chapter 2: Installation

Doc. 0600-3120-2000

Watlow Anafaze

33

Configuring Outputs

As you choose outputs for control and alarms, bear in mind

the following points:

You can enable or disable the control outputs. By default,

heat outputs are enabled and cool outputs are disabled.

You can program each control output individually for on/

off, time proportioning, distributed zero-crossing or Se-

rial DAC control.

You can individually program each control output for di-

rect or reverse action.

Alarm outputs other than the global alarm are non-latch-

ing. See Global Alarm on page 97.

Alarms can be suppressed during process start up and for

preprogrammed durations. See Power Up Alarm Delay

on page 128.

Alarm outputs can be configured, as a group, to sink to

output during an alarm or stop current flow during an

alarm. See Digital Output Alarm Polarity on page 129.

Control and Alarm Output Connections

Typically control and alarm outputs use external optically-

isolated solid state relays (SSRs). SSRs accept a 3 to 32 Vdc

input for control, and some can switch up to 100 Amps at 480

Vac. For larger currents, use silicon control rectifier (SCR)

power controllers up to 1000 Amps at 120 to 600 Vac. You

can also use SCRs and a Serial DAC for phase-angle fired

control.
The control and alarm outputs are open collector outputs ref-

erenced in the D8’s common. Each output sinks up to 60

mAdc to the controller common when on.

NOTE!

Control outputs are sink outputs. They sink
current when the output is on. Connect them
to the negative side of solid state relays.

Figure 2.18 shows sample heat, cool and alarm output connec-

tions.

Figure 2.18 Sample Heat, Cool and Alarm

Output Connections

Heat Output

Cool Output

Alarm Output

+5 Vdc

+

-

+

-

+

-

SSR

SSR

SSR

TB50 or TB18