Chapter 6: Menu and Parameter Reference

Series D8 User’s Guide

152

Watlow Anafaze

Doc. 0600-3120-2000

Digital Inputs

This parameter indicates the states of the eight digital inputs.

A 1 indicates that the input is connected to controller common

(on). A 0 indicates an open circuit (off).
To test an input, short it to controller common. When the input

is shorted, its input state should be 1. For detailed instructions,

see Digital Input Test on page 27.
The controller display shows the states of digital inputs 1 to 8

from left to right.

Values:

0 if the input is off, 1 if the input is on

DeviceNet Object:

Global (6B hex)

Keypad Test

To test the keypad, press <. This screen will appear:

To test a key, press it. If the key is working properly, an icon

for that key appears.
When you are done testing the keypad, press >> to return to

the Keypad test parameter.

DeviceNet Object:

None

Display Test

Displays two screens with alternate pixels lit. Press < to enter
test, press > or < to switch pattern. Press

x

to end the test.

DeviceNet Object:

None

lDigital inputsr
00000000 1=on

lKeypad test r
press d to begin

uu Ends test
key pressed=

lDisplay test r
Press d to begin