Digital inputs, Keypad test, Display test – Watlow Series D8 User Manual
Page 170: Digital inputs 152, Keypad test 152, Display test 152

Chapter 6: Menu and Parameter Reference
Series D8 User’s Guide
152
Watlow Anafaze
Doc. 0600-3120-2000
Digital Inputs
This parameter indicates the states of the eight digital inputs.
A 1 indicates that the input is connected to controller common
(on). A 0 indicates an open circuit (off).
To test an input, short it to controller common. When the input
is shorted, its input state should be 1. For detailed instructions,
see Digital Input Test on page 27.
The controller display shows the states of digital inputs 1 to 8
from left to right.
Values:
0 if the input is off, 1 if the input is on
DeviceNet Object:
Global (6B hex)
Keypad Test
To test the keypad, press <. This screen will appear:
To test a key, press it. If the key is working properly, an icon
for that key appears.
When you are done testing the keypad, press >> to return to
the Keypad test parameter.
DeviceNet Object:
None
Display Test
Displays two screens with alternate pixels lit. Press < to enter
test, press > or < to switch pattern. Press
x
to end the test.
DeviceNet Object:
None
lDigital inputsr
00000000 1=on
lKeypad test r
press d to begin
uu Ends test
key pressed=
lDisplay test r
Press d to begin