Series D8 User’s Guide

Chapter 4: Operation and Setup

Doc. 0600-3120-2000

Watlow Anafaze

95

The RTD alarms are enabled on any channel with Input Type

set to RTD.

Restore Automatic Control After a Sensor Failure

This feature returns a loop to automatic control after a failed

sensor is repaired. To enable this feature:

Choose a digital input for the RestoreAuto parameter in

the Control menu.

Connect the digital input to the dc common terminal on

the controller.

Process Alarms

The D8 has four process alarms, each of which you can con-

figure separately for each loop:

Alarm low

Alarm high

Low deviation alarm

High deviation alarm

What Happens if a Process Alarm Occurs?

If a process alarm occurs, the controller does the following:

Shows an alarm code on the display. See Alarm Displays

on page 81.

Activates the global alarm output. See Global Alarm on

page 97.

Activates the digital output that is assigned to the process

alarm (if applicable). The digital output remains active

until the process variable returns within the correspond-

ing limit and hysteresis. The alarm output deactivates

when the process returns to normal.

Process Alarm Outputs

Any digital output that is not used as a control output can be

assigned to one or more process alarms.
The controller activates the output if any alarm assigned to the

output is active. Process alarm outputs are non-latching—that

is, the output is deactivated when the process returns to nor-

mal, whether or not the alarm has been acknowledged.
Specify the active state of process alarm outputs at the D/O
alarm polarity

setting in the Global setup menu.