Low deviation output, Alarm low set point, Alarm low function – Watlow Series D8 User Manual
Page 164: Alarm low output, Low deviation output 146, Alarm low set point 146, Alarm low function 146, Alarm low output 146
Chapter 6: Menu and Parameter Reference
Series D8 User’s Guide
146
Watlow Anafaze
Doc. 0600-3120-2000
Low Deviation Output
Choose a digital output to activate when the low deviation
alarm occurs. You cannot choose an output that is in use for
closed-loop control or for the Serial DAC clock.
Values:
none (0) or output 1 to 18 (1 to 18). Values in paren-
theses are for communications.
Default:
none (0)
DeviceNet Object:
Alarm (67 hex)
Alarm Low Set Point
Enter the set point at which the low alarm activates. The low
alarm activates if the process variable drops below this value.
For more information, see Process Alarms on page 95.
Values:
For a thermocouple or RTD input, any value within
the input range (see Table 6.7 on page 131). For a process or
pulse input, any value between the Input range low and Input
range high
parameters.
Default:
0
Decimal Placement for DeviceNet:
for Numeric Values on page 59.
DeviceNet Object:
Alarm (67 hex)
Alarm Low Function
Choose whether the alarm functions as an alarm or as a boost
output, or disable the alarm.
Values:
Default:
off
DeviceNet Object:
See Alarm Acknowledge on page 153 and
Alarm Low Output
Choose a digital output to activate when the low alarm occurs.
You cannot choose an output that is in use for closed-loop
control or for the Serial DAC clock.
Values:
none (0) or output 1 to 18 (1 to 18). Values in paren-
theses are for communications.
Default:
none (0)
DeviceNet Object:
Alarm (67 hex)
l01 LoDeviationr
outputbnone
l01 Alarm low r
SP b 0°C
l01 Alarm low r
func boff
l01 Alarm low r
outputbnone