Series D8 User’s Guide

Chapter 6: Menu and Parameter Reference

Doc. 0600-3120-2000

Watlow Anafaze

127

Values:

1=true (0) or 0=true (1). Values in parentheses are

for communications.
Default:

1=true (0)

DeviceNet Object:

Global (6B hex)

Table 6.4

Digital Input States Required to
Load Each Job

Mode Override

Choose the digital input to use for the mode override feature.

When the input is activated, the controller sets all loops to

manual mode at the output levels specified at the Sensor fail
heat output

and Sensor fail cool output parameters in the Out-

put

menu.

Use the Mode override D/I active parameter to choose which

signal state activates the mode override feature.

Values:

enabled by D/I1 to enabled by D/I8 (1 to 8) or dis-

abled

(0). Values in parentheses are for communications.

Default:

disabled (0)

DeviceNet Object

: Global (6B hex)

WARNING!

Do not rely solely on the mode override
feature to shut down your process. Install ex-
ternal safety devices or overtemperature de-
vices for emergency shutdowns.

Job

Digital Input

1

2

3

1

F

F

F

2

T

F

F

3

F

T

F

4

T

T

F

5

F

F

T

6

T

F

T

7

F

T

T

8

T

T

T

lMode override r
bdisabled