beautypg.com

Figure 2.17—digital output wiring 32 – Watlow Series D8 User Manual

Page 50

background image

Chapter 2: Installation

Series D8 User’s Guide

32

Watlow Anafaze

Doc. 0600-3120-2000

Table 2.4

Digital Output States and Values
Stored in the Controller

1

Read and write these values through communications.

All digital outputs sink current to controller common when

on. The load may powered by the 5 Vdc supplied by the con-

troller at the TB50, or by an external power supply. When us-

ing an external power supply, bear in mind:

The D8 power supply available from Watlow Anafaze

includes a 5 Vdc supply. When using it to supply output

loads, connect the 5 Vdc common to the 15 Vdc common

at the power supply.

Do not exceed +24 volts.

If you connect the external load to earth ground, or if you

cannot connect it as shown in Figure 2.17, then use a sol-

id state relay.

The outputs conduct current when they are on. The maximum

current sink capability is 60 mA at 24 Vdc. The outputs cannot

“source” current to a load.

Figure 2.17 Digital Output Wiring

State

Value

1

Description

Off

0

Open circuit

On

1

Sinking current to controller common

Digital Output 1

Digital Output 2

Control Common

+5 Vdc

Loads

Digital Output 1
Digital Output 2

Using External Power Supply

Do not connect

External

Power

+

-

TB50 or TB18

Using Internal Power Supply

Loads

Supply

TB50 or TB18

to earth ground or

equipment ground