Test digital output 1 to 20, Parameters only available via communications, Alarm acknowledge – Watlow Series D8 User Manual
Page 171: Alarm enable, Test digital output 1 to 20 153, Parameters only available via communications 153, Alarm acknowledge 153, Alarm enable 153

Series D8 User’s Guide
Chapter 6: Menu and Parameter Reference
Doc. 0600-3120-2000
Watlow Anafaze
153
Test Digital Output 1 to 20
Use the Test D/O parameter to manually toggle a digital out-
put on and off. Choose on to sink the current from the output
to the controller common. Choose off to stop the current flow.
For instructions, see Digital Output Test on page 26. You can-
not toggle an output that is enabled for control.
Values:
off (0) or on (1)
Default:
off (0)
DeviceNet Object:
Global (6B hex)
NOTE!
When you exit the I/O tests menu, all outputs
that were forced on are turned off.
Parameters Only Available via Communications
These parameters are available only via communications.
They are not accessible through the controller keypad.
Alarm Acknowledge
Indicates whether an alarm has been acknowledged. To ac-
knowledge an alarm, clear the bit for that alarm. Table 6.17 on
page 155 shows which bit corresponds to each alarm.
This parameter is available only via communications.
Values:
Unacknowledged (1) or acknowledged (0)
DeviceNet Object:
Alarm (67 hex)
Alarm Enable
Enable or disable an alarm. Table 6.16 on page 154 shows the
bit to set or read for each alarm. This parameter is available
only via communications.
Values:
Disabled (0) or enabled (1)
Default:
Disabled (0)
DeviceNet Object:
Alarm (67 hex)
lTest D/O 1 r
boff