beautypg.com

Setting up cascade control, How the secondary set point is determined, Setting up cascade control 100 – Watlow Series D8 User Manual

Page 118: How the secondary set point is determined 100

background image

Chapter 4: Operation and Setup

Series D8 User’s Guide

100

Watlow Anafaze

Doc. 0600-3120-2000

To complete this configuration, the output for loop 2 must be

configured to provide the 4 to 20 mA analog signal (via the

Serial DAC) that is required by the data logger.
When setup is completed, the controller will produce an out-

put on loop 2 which is linear and proportional to the loop 1

process variable.

Setting Up Cascade Control

Cascade control is used to control thermal systems with long

lag times, which cannot be as accurately controlled with a sin-

gle control loop. The output of the first (primary) loop is used

to adjust the set point of the second (secondary) loop. The sec-

ondary loop normally executes the actual control.
Some applications, such as aluminum casting, use two-zone

cascade control where the primary output is used for the pri-

mary heat control and the cascaded output is used for boost

heat. You can use the primary heat output for both control and

for determining the set point of the secondary loop.

How the Secondary Set Point is Determined

The set point of the secondary loop is determined according to

the heat and cool output values from the primary loop and

user-specified cascade parameters:

If the primary loop has both heat and cool outputs, then

the set point of the secondary loop is equal to the Cas-
cade low SP

parameter when the cool output is at 100

percent, and is equal to the Cascade high SP when the

heat output is at 100 percent. See Figure 4.9.

If the primary loop has only a heat output, then the set

point of the secondary loop is equal to the Cascade low
SP

parameter when the heat output is at 0 percent, and is

equal to the Cascade high SP parameter when the heat

output is at 100 percent. See Figure 4.10.

If the primary loop has only a cool output, then the set

point of the secondary loop is equal to the Cascade low
SP

parameter when the cool output is at 100 percent, and

is equal to the Cascade high SP parameter when the cool

output is at 0 percent.