Chapter 3: Communicating by DeviceNet

Series D8 User’s Guide

70

Watlow Anafaze

Doc. 0600-3120-2000

NOTE!

All successful explicit message responses
from a Set service will contain no data. The
response will be a two-byte message con-
taining the requester’s node address and
service code (with R/R bit set).

Control Object

The Control Object provides read/write access to all control

parameters. Instance 0 of this object contains the class at-

tributes listed in Table 3.25. The four-loop controller has four

additional instances, and the eight-loop controller has eight

additional instances, each containing the attributes listed in

Table 3.26. Instance 1 corresponds to loop 1, instance 2 cor-

responds to loop 2, and so on.

Table 3.24 Control Class and Services

Table 3.25 Control Class Attributes (Instance 0)

Table 3.26 Control Instance Attributes

(Instances 1 to 4 or 8)

Class Code

66 hex

Class Services

0E hex Get Attribute Single

Instance Services

0E hex Get Attribute Single
10 hex Set Attribute Single

Attribute

Access

Name

Type

Description

1 (1 hex)

Get

Revision

UINT

Revision of this object

2 (2 hex)

Get

Max Instance

UINT

Maximum instances of this object (8)

3 (3 hex)

Get

Number of

Instances

UINT

Number of object instances

Attribute

Access

Name

Type

Description

100 (64 hex)

Get/Set

Heat Proportional Band

UINT

See page 136.

101 (65 hex)

Get/Set

Cool Proportional Band

UINT

See page 136.

102 (66 hex)

Get/Set

Heat Integral

UINT

See page 137.

103 (67 hex)

Get/Set

Cool Integral

UINT

See page 137.

104 (68 hex)

Get/Set

Heat Derivative

USINT

See page 137.

105 (69 hex)

Get/Set

Cool Derivative

USINT

See page 137.

106 (6A hex)

Get/Set

Heat Manual Reset

UINT

See page 137.

107 (6B hex)

Get/Set

Cool Manual Reset

UINT

See page 137.

108 (6C hex)

Get/Set

Heat Filter

USINT

See page 137.