Chapter 3: Communicating by DeviceNet
Series D8 User’s Guide
70
Watlow Anafaze
Doc. 0600-3120-2000
NOTE!
All successful explicit message responses
from a Set service will contain no data. The
response will be a two-byte message con-
taining the requester’s node address and
service code (with R/R bit set).
Control Object
The Control Object provides read/write access to all control
parameters. Instance 0 of this object contains the class at-
tributes listed in Table 3.25. The four-loop controller has four
additional instances, and the eight-loop controller has eight
additional instances, each containing the attributes listed in
Table 3.26. Instance 1 corresponds to loop 1, instance 2 cor-
responds to loop 2, and so on.
Table 3.24 Control Class and Services
Table 3.25 Control Class Attributes (Instance 0)
Table 3.26 Control Instance Attributes
(Instances 1 to 4 or 8)
Class Code
66 hex
Class Services
0E hex Get Attribute Single
Instance Services
0E hex Get Attribute Single
10 hex Set Attribute Single
Attribute
Access
Name
Type
Description
1 (1 hex)
Get
Revision
UINT
Revision of this object
2 (2 hex)
Get
Max Instance
UINT
Maximum instances of this object (8)
3 (3 hex)
Get
Number of
Instances
UINT
Number of object instances
Attribute
Access
Name
Type
Description
100 (64 hex)
Get/Set
Heat Proportional Band
UINT
101 (65 hex)
Get/Set
Cool Proportional Band
UINT
102 (66 hex)
Get/Set
Heat Integral
UINT
103 (67 hex)
Get/Set
Cool Integral
UINT
104 (68 hex)
Get/Set
Heat Derivative
USINT
105 (69 hex)
Get/Set
Cool Derivative
USINT
106 (6A hex)
Get/Set
Heat Manual Reset
UINT
107 (6B hex)
Get/Set
Cool Manual Reset
UINT
108 (6C hex)
Get/Set
Heat Filter
USINT