Chapter 7: Troubleshooting and Reconfiguring

Series D8 User’s Guide

160

Watlow Anafaze

Doc. 0600-3120-2000

Responding to a Process Alarm

Your response to an alarm depends upon the alarm function

setting, as explained in Table 7.1.

Table 7.1

Operator Response to Process
Alarms

Ambient Warning

The Ambient Warning indicates that the controller is within

5°C of its operating temperature limits. If an Ambient Warn-

ing occurs, the alarm code AW (flashing) is displayed, and the

global alarm output is turned on. Acknowledging the alarm

turns off the global alarm output. The error clears when the

condition no longer exists and the alarm has been acknowl-

edged.
If the controller displays the AW alarm code:
1. Acknowledge the alarm.
2. Adjust the ambient temperature to a more appropriate level.

Failed Sensor Alarms

When a failed sensor alarm occurs, the controller switches to

the single loop display for the loop with the alarm and displays

an alarm code (see Alarm Displays on page 81).
A failed sensor alarm clears once it has been acknowledged

and the sensor is repaired. For more information about the

causes of failed sensor alarms, see Failed Sensor Alarms on

page 93.

System Alarms

If the controller detects a hardware problem, it displays an

alarm message, and with the exception of the Low Power

Alarm

Function

Operator Response

Boost

The operator does not need to acknowledge

the alarm. The alarm clears automatically

when the process variable returns within lim-

its.

Standard

Acknowledge the alarm by pressing x on

the keypad or via communications. The

alarm clears after the operator acknowl-

edges it and the process variable returns

within the limits.