Setting up and tuning pid loops, Proportional band settings, Integral settings – Watlow Series D8 User Manual
Page 133: Setting up and tuning pid loops 115, Proportional band settings 115, Integral settings 115, Table 5.1—proportional band settings 115
Series D8 User’s Guide
Chapter 5: Tuning and Control
Doc. 0600-3120-2000
Watlow Anafaze
115
Setting Up and Tuning PID Loops
After installing your control system, tune each control loop
and then set the loop to automatic control. When tuning a
loop, choose PID parameters that will best control the process.
This section gives PID values for a variety of heating and
cooling applications.
NOTE!
Tuning is a slow process. After adjusting a
loop, allow about 20 minutes for the change
to take effect.
Proportional Band Settings
Table 5.1 shows proportional band settings for various tem-
peratures in degrees Fahrenheit or Celsius.
Table 5.1
Proportional Band Settings
As a general rule, set the proportional band to ten percent of
the set point below 1000
°
and five percent of the set point
above 1000
°
. This setting is useful as a starting value.
Integral Settings
The controller’s integral parameter is set in seconds per re-
peat. Some other products use an integral term called reset, in
units of repeats per minute. Table 5.2 shows integral settings
versus reset settings.
Temperature
Set Point
PB
Temperature
Set Point
PB
Temperature
Set Point
PB
-100 to 99
20
1100 to 1199
75
2200 to 2299
135
100 to 199
20
1200 to 1299
80
2300 to 2399
140
200 to 299
30
1300 to 1399
85
2400 to 2499
145
300 to 399
35
1400 to 1499
90
2500 to 2599
150
400 to 499
40
1500 to 1599
95
2600 to 2699
155
500 to 599
45
1600 to 1699
100
2700 to 2799
160
600 to 699
50
1700 to 1799
105
2800 to 2899
165
700 to 799
55
1800 to 1899
110
2900 to 2999
170
800 to 899
60
1900 to 1999
120
3000 to 3099
175
900 to 999
65
2000 to 2099
125
3100 to 3199
180
1000 to 1099
70
2100 to 2199
130
3200 to 3299
185