Heat/Cool Integral

Enter the integral constant. A larger value yields less integral

action.

Values:

0 (off) to 6000 seconds per repeat

Default:

For the Heat integral parameter, 180. For the Cool

integral

parameter, 60.

DeviceNet Object:

Control (66 hex)

Heat/Cool Derivative

Enter the derivative constant. A larger value yields greater de-

rivative action.

Values:

0 to 255 seconds

Default:

0

DeviceNet Object:

Control (66 hex)

Heat/Cool Manual Reset

A process that uses only proportional control settles at a point

above or below the set point; it never reaches the set point.

This is known as offset or droop. At this parameter, enter the

power level required to maintain set point to compensate for

this offset.

Values:

0 to 100% (0 to 1000). Values in parentheses are for

communications.
Default:

0% (0)

Decimal Placement for DeviceNet:

See Decimal Placement

for Percentage Values on page 60.
DeviceNet Object:

Control (66 hex)

Heat/Cool Filter

Use this parameter to dampen the response of the heat or cool

output. The output responds to a change by going to approxi-

mately two-thirds of its final value within the specified num-

ber of scans. A larger value results in a slower response to

changes in the process variable.

Values:

0 (off) to 255

Default:

3

DeviceNet Object:

Control (66 hex)

l01 Heat inte- r
gral b 180 sec/R

l01 Heat de- r
rivativeb 0 sec

l01 Heat manualr
reset b 0%

l01 Heat filterr
b 3 scans