6 quick stop active, 7 fault response active, Quick stop active – Lenze E94AxHE Technology Application CiA402 Device profile User Manual

Page 58: Fault response active

background image

9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Device control

58

L

EDS94TA11010xxxx EN 1.2 - 03/2010

3.7.3.6

Quick stop active

This device state is active if

Quick stop

is executed or active.

 Only the parameters of the controller can be changed which do not require controller

inhibit.

 The motor brake, if available, is opened.
 The motor has torque.

3.7.3.7

Fault response active

If a minor error occurs, i.e. the drive is still able to operate the motor in a controlled manner,

this device state becomes active and the drive is braked to standstill irrespective of the

defined setpoint within the deceleration time set in

Quick stop

.

 Only the parameters of the controller can be changed which do not require controller

inhibit.

 The motor brake, if available, is opened.
 The operation is enabled, the motor has torque.

Bit pattern for device state "Quick stop active" in

0x6041

(status word):

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Warning

Switch on

disabled

Quick stop

Voltage

enabled

Fault

Operation

enabled

Switched on

Ready to switch

on

X

0

0

X

0

1

1

1

Note!

The "

Enable operation

" command serves to deactivate an active quick stop

again.

Bit pattern for "Fault response active" device command in

0x6041

(status word):

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Warning

Switch on

disabled

Quick stop

Voltage

enabled

Fault

Operation

enabled

Switched on

Ready to switch

on

X

0

X

X

1

1

1

1

Note!

After the "

Quick stop

" basic function has been executed, i.e. the drive is at

standstill, it is automatically changed to the "

Fault

" device state.

The "

Fault

" device state can only be left using the "

Reset fault

" command if the

error cause is removed.