2 switch on disabled, 3 ready to switch on, Switch on disabled – Lenze E94AxHE Technology Application CiA402 Device profile User Manual
Page 56: Ready to switch on, Ce status from, Ready to switch, It is changed back to the device state, I.e. the switch on inhibit is active

9400 Technology applications | CiA402 device profile
Parameter setting & configuration
Device control
56
L
EDS94TA11010xxxx EN 1.2 - 03/2010
3.7.3.2
Switch on disabled
This is the controller's status after the device has been initialised successfully.
The process data monitoring is active.
Communication is possible.
DC-bus voltage is available.
The controller can be parameterised.
The motor brake, if available, is closed.
The operation is inhibited.
3.7.3.3
Ready to switch on
This is the device status of the controller after the device has been initialised successfully
and after the controller has received the "
" command.
The process data monitoring is active.
Communication is possible.
DC-bus voltage is available.
The controller can be parameterised.
The motor brake, if available, is closed.
The operation is inhibited.
Bit pattern for device state "Switch on disabled" in
(status word):
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Warning
Switch on
disabled
Quick stop
Voltage
enabled
Fault
Operation
enabled
Switched on
Ready to switch
on
X
1
X
X
0
0
0
0
Bit pattern for "Ready to switch on" device state in
(status word):
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Warning
Switch on
disabled
Quick stop
Voltage
enabled
Fault
Operation
enabled
Switched on
Ready to switch
on
X
0
1
X
0
0
0
1
Note!
It is also changed to this device state if in the device states "
" command is tripped.
The change to the sequential state "
" is caused by the tripping of the