9400 Technology applications | CiA402 device profile

Parameter setting & configuration

Cyclic synchronous velocity mode (IEC 61800-7)

154

L

EDS94TA11010xxxx EN 1.2 - 03/2010

3.13.6

Control commands & status information

The CiA402 (

0x6040

) control word serves to execute control commands in the "cyclic

synchronous velocity mode":

The CiA402 status word (

0x6041

) serves to output the following status information in the

"Cyclic synchronous velocity mode":

Control word

Status Function

Bit 4

0 Reserved (bit must be set to "0")

Bit 5

0 Reserved (bit must be set to "0")

Bit 6

0 Reserved (bit must be set to "0")

Bit 8

0 Ê 1 Stop

Status word

Status Meaning

Bit 12

0 "Cyclic synchronous velocity mode" is not active
1 "Cyclic synchronous velocity mode" is active

Bit 13

0 Reserved (bit is always set to "0")