Appendix C Lightning Protection of the Switch

C-2

Caution:

z

Make sure that the arrester is well grounded before using the lightning arrester for

power.

z

After inserting AC power cord plug of switch into the socket of lightning arrester, if

the green LED is on and the red LED does not alarm, it means that the lightning

arrester of power is running and the function of lightning protection has taken effect.

z

Pay adequate attention if the red LED is on. You should correctly locate the problem,

whether it is caused because the ground wire of the arrester is not well grounded or

because the live and zero wires are connected in reverse direction. You may check

that in the following way. When the red LED is on, use a multimeter to examine

polarity at the power socket of the arrester. If it is same to that of the power socket in

the equipment room, it means that arrester is not well grounded. If it is adverse to

that of the power socket in the equipment room, it means that the power socket of

the arrester is set to the reverse polarity. In this case, you should open the power

socket of arrester to correct polarity. After that, if the red LED still alarms, it means

that the arrester is not well grounded yet.