Iv. fastening retaining nut of anchor plate, B.3.9 insulation test, B.3.10 floor recovery – H3C Technologies H3C S9500 Series Switches User Manual
Page 182
Installation Manual
H3C S9500 Series Routing Switches
Appendix B Installation of B68 Cabinet
B-31
IV. Fastening retaining nut of anchor plate
Fasten the retaining nut of the anchor plate on the anchor plate according to part B in
Figure B-33, and then fasten the bolt force moment to 45 Nm.
B.3.9 Insulation Test
Measure the resistance value between the retaining bolt and the anchor plate with a
Multimeter. If the resistance value measured is larger than five meg-ohm, it means that
the insulation is normal. Otherwise, it means that the cabinet is not insulated from the
earth. In this case, remove all anchor plate parts to check whether the insulating
covering or insulating washer is installed or whether the insulating parts are damaged.
Afterwards, reinstall the anchor plate and repeat the insulation test.
B.3.10 Floor Recovery
According to the actual site status, cut the raised floor around the cabinet and then
recover the floor. Figure B-34 shows the raised floor recovery installation and Figure
B-35 shows the B68-22 cabinet installation in the equipment room with the raised floor.
Caution:
The framework of the raised floor can be installed on the side floor bracket according to
the actual circumstance, as shown in Figure B-34.
Cut the raised floor as little as possible.
- H3C S7500E Series Switches H3C S7500 Series Switches H3C S5800 Series Switches H3C S5820X Series Switches H3C S5500 Series Switches H3C S5120 Series Switches H3C S3610[S5510] Series Switches H3C S3600 Series Switches H3C S3100 Series Switches OAA For Routers H3C WX6000 Series Access Controllers H3C WX5000 Series Access Controllers H3C WX3000 Series Unified Switches H3C LSQM1WCMB0 Access Controller Module H3C LSBM1WCM2A0 Access Controller Module H3C WA2600 Series WLAN Access Points H3C WA2200 Series WLAN Access Points H3C SecPath F1000-E H3C SecPath F1000-A H3C SecPath F1000-S H3C SecPath F100-A H3C SecPath F100-C-EI H3C SecPath V100-E H3C SecCenter iTAS H3C Device Manager