A.4 engineering labels for power cables, A.4.1 labels for dc power cables, I. meaning of the label – H3C Technologies H3C S9500 Series Switches User Manual
Page 147

Installation Manual
H3C S9500 Series Routing Switches
Appendix A Engineering Labels for Cables
A-13
Figure A-12 Example of the label on the optical fiber between the device and the ODF
“ODF-G01-01-01-R” indicates that the local end of the optical fiber is connected with
the optical receiving terminal on Row 01, Column 01 of the ODF in Row G Column 01 in
the machine room.
“A01-01-05-05-R” indicates that the opposite end of the optical fiber is connected with
Optical Receiving Interface 5 on Slot 05, frame 01 in the cabinet on Row A, Column 01
in the machine room.
A.4 Engineering Labels for Power Cables
A.4.1 Labels for DC Power Cables
The labels are affixed to the DC cables that provide power for the cabinets, and the
protection grounding cables, including the -48V, PGND, and BGND cables. The labels
for DC power cables are affixed to one side of the identification plates on cable ties.
I. Meaning of the label
Table A-5 shows the information carried on the labels for the DC power cables:
Table A-5 Information on labels affixed to the DC power cables
Content
Meaning
MN(BC)--48V1
MN(BC)--48V2
MN(BC)-BGND
MN(BC)-PGND
MN(BC): BC is written right under MN.
On the loaded cabinet side, only MN is used to identify the
cabinet.
On the power cabinet side, MN identifies the row and column
number of the power distribution equipment like the control
cabinet and distribution box, BC identifies the row and
column number of the -48V connecter (if there is no row
number or column number, or the connecter can be identified
without them, BC can be omitted). BGND and PGND have no
row and column number for identification.
The label only carries location information about the opposite equipment, the control
cabinet or the distribution box, while information of the local end is not necessary. Table
A-5ists the information of two -48V power supplies on the label. The information for
other DC voltages (such as 24V, 60V) should be given in similar methods.
- H3C S7500E Series Switches H3C S7500 Series Switches H3C S5800 Series Switches H3C S5820X Series Switches H3C S5500 Series Switches H3C S5120 Series Switches H3C S3610[S5510] Series Switches H3C S3600 Series Switches H3C S3100 Series Switches OAA For Routers H3C WX6000 Series Access Controllers H3C WX5000 Series Access Controllers H3C WX3000 Series Unified Switches H3C LSQM1WCMB0 Access Controller Module H3C LSBM1WCM2A0 Access Controller Module H3C WA2600 Series WLAN Access Points H3C WA2200 Series WLAN Access Points H3C SecPath F1000-E H3C SecPath F1000-A H3C SecPath F1000-S H3C SecPath F100-A H3C SecPath F100-C-EI H3C SecPath V100-E H3C SecCenter iTAS H3C Device Manager