Installation Manual
H3C S9500 Series Routing Switches

Appendix A Engineering Labels for Cables

A-14

II. Example of the label

Make sure that labels are affixed in correction direction. That is, after the cable ties are

bundled onto the cable, the identification plates with the labels should face up, and the

text on the labels in the same cabinet should be in the same direction, as shown in

Figure A-13

(1)

(2)

TO:

A01 -48V2

B08

TO:

B03 -48V2

(1)

(2)

TO:

A01 -48V2

B08

TO:

B03 -48V2

Figure A-13 Example of the labels on the DC power cable

In Figure A-13, (1) indicates the label on the loaded cabinet side, which carries the

information about the position of the cable on the power distribution box. (2) indicates

the label on the distribution box side, which carries the information about the position of

the cable on the loaded cabinet side.

On the loaded cabinet side, the label marked with “A01/B08--48V2” on the cable

indicates that the cable is -48V2 DC supply, which is from the 8

th

connecter on the

second row of -48V bus bar in the cabinet on Row A, and Column 1 in the machine

room.

On the distribution box side, the label marked with “B03--48V2” indicates that the cable

is -48V2 DC supply, which is from the loaded cabinet on Row B, Column 03 in the

machine room.