Chapter 6 Switch Monitoring and Maintenance
6-7
6.2.3 Replacing and Cleaning the Air Filter of PSU
The air filter of AC PSU and DC PSU can be replaced in a similar way even though they
have different shapes.
Caution:
You are strongly recommended to clean the air filter semimonthly to guarantee
adequate ventilation.
I. Removing and cleaning the air filter of PSU
Step 1: Clutch the air filter by the upper and lower edges with your index finger and the
thumb.
Step 2: Pull the air filter out with an even strength.
Step 3: Take the black air filter mesh out.
Step 4: Clean the mesh and dry it, taking care not to rub it.
Step 5: Place the dry black mesh back in position again.
(1) PSU
(2) Air filter
(3) Air filter cover
Figure 6-3 Remove the air filter of DC PSU
- H3C S7500E Series Switches H3C S7500 Series Switches H3C S5800 Series Switches H3C S5820X Series Switches H3C S5500 Series Switches H3C S5120 Series Switches H3C S3610[S5510] Series Switches H3C S3600 Series Switches H3C S3100 Series Switches OAA For Routers H3C WX6000 Series Access Controllers H3C WX5000 Series Access Controllers H3C WX3000 Series Unified Switches H3C LSQM1WCMB0 Access Controller Module H3C LSBM1WCM2A0 Access Controller Module H3C WA2600 Series WLAN Access Points H3C WA2200 Series WLAN Access Points H3C SecPath F1000-E H3C SecPath F1000-A H3C SecPath F1000-S H3C SecPath F100-A H3C SecPath F100-C-EI H3C SecPath V100-E H3C SecCenter iTAS H3C Device Manager