beautypg.com

Iii. fastening retaining nut of anchor plate, B.2.7 insulation test – H3C Technologies H3C S9500 Series Switches User Manual

Page 162

background image

Installation Manual
H3C S9500 Series Routing Switches

Appendix B Installation of B68 Cabinet

B-11

(1) Retaining nut of anchor plate

(2) Anchor plate of the B68-22 cabinet

(3) Cabinet foot

(4) Insulating washer of anchor plate

(5) Bolt M12%70

(6) Spring washer Φ12

(7) Big flat washer Φ12

(8) Insulating covering

(9) Expansion tube

(10) Expansion nut

Figure B-11

Fastening of anchor plate of the B68-22 cabinet

III. Fastening retaining nut of anchor plate

Fasten the retaining nut of the anchor plate according to part B in Figure B-11.

B.2.7 Insulation Test

Measure the resistance value between the fixing bolt M12

× 70 and the anchor plate

with a Multimeter. If the resistance value measured is larger than five meg-ohm, it
means the insulation is normal. Otherwise, it means that the cabinet is not insulated