Chapter 4 Parameters|

4-44

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

01.05

01.03

01.01

01.06

01.04

01.02

01.00

01.07

01.08

V/f Curve

Voltage

Frequency

Output Frequency
Lower Limit

Output Frequency
Upper Limit

The limit of
Output
Frequency

Mid-point
Freq.

Maximum
Output
Frequency

Maximum
Output
Voltage

Mid-point
Voltage

Minimum
Output
Voltage

Minimum
Output
Freq.

Maximum Voltage
Frequency
(Base Frequency)

01.08

Output Frequency Lower Limit

Unit: 0.1

Settings

0.0 to 100.0%

Factory Setting: 0.0

The Upper/Lower Limits are to prevent operation errors and machine damage.

If the Output Frequency Upper Limit is 50Hz and the Maximum Output Frequency is 60Hz, the

Output Frequency will be limited to 50Hz.

If the Output Frequency Lower Limit is 10Hz, and the Minimum Output Frequency (Pr.01.05) is

set to 1.0Hz, then any Command Frequency between 1.0-10Hz will generate a 10Hz output

from the drive.

This parameter must be equal to or less than the Output Frequency Upper Limit (Pr.01.07).

The Output Frequency Lower Limit value = (Pr.01.00 * Pr.01.08) /100.

01.09

Acceleration Time 1 (Taccel 1)

Unit: 0.1/0.01

01.10

Deceleration Time 1 (Tdecel 1)

Unit: 0.1/0.01

01.11

Acceleration Time 2 (Taccel 2)

Unit: 0.1/0.01

01.12

Deceleration Time 2 (Tdecel 2)

Unit: 0.1/0.01

Settings

0.1 to 600.0 sec / 0.01 to 600.0 sec

Factory Setting: 10.0

Acceleration/deceleration time 1 or 2 can be switched by setting the external terminals MI3~

MI12 to 7 (set Pr.04.05~Pr.04.08 to 7 or Pr.11.06~Pr.11.11 to 7).

01.19

Accel/Decel Time Unit

Factory Setting: 0

Settings

0

Unit: 0.1 sec

1

Unit:

0.01

sec