Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-77

Settings Function Description

15

PID function

disabled

When an input ON with this setting is ON, the PID function will be

disabled.

16 Output

Shutoff

Stop

AC motor drive will stop output and the motor free run if one of

these settings is enabled. If the status of terminal is changed, AC

motor drive will restart from 0Hz.

17

Parameter lock

enable

When this setting is enabled, all parameters will be locked and

write parameters is disabled.

18

Operation

Command

Selection (Pr.02.01

setting/external

terminals)

ON: Operation command via Ext. Terminals

OFF: Operation command via Pr.02.01 setting

When the settings 18, 19 and 20 are ON at the same time, the

priority should be setting 18 > setting19 > setting20.

19

Operation

Command

Selection (Pr 02.01

setting/Digital

Keypad)

ON: Operation command via Digital Keypad

OFF: Operation command via Pr.02.01 setting

When the settings 18, 19 and 20 are ON at the same time, the

priority should be setting 18 > setting19 > setting20.

20

Operation

Command

Selection (Pr 02.01

setting/

Communication)

ON: Operation command via Communication

OFF: Operation command via Pr.02.01 setting

When the settings 18, 19 and 20 are ON at the same time, the

priority should be setting 18 > setting19 > setting20.

21 Forward/Reverse

This function has top priority to set the direction for running (If

“Pr.02.04=0”)

22

Source of second

frequency

command enabled

Used to select the first/second frequency command source. Refer

to Pr.02.00 and 02.09.

ON: 2

nd

Frequency command source

OFF: 1

st

Frequency command source