Chapter 4 Parameters|

4-22

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Parameter Explanation

Settings

Factory

Setting

Customer

0: Operation stops after momentary power
loss

1: Operation continues after momentary

power loss, speed search starts with the
Master Frequency reference value

08.04

Momentary Power
Loss Operation
Selection

2: Operation continues after momentary

power loss, speed search starts with the
minimum frequency

0

08.05

Maximum Allowable
Power Loss Time

0.1 to 5.0 sec

2.0

08.06

Base-block Speed
Search

0: Disable speed search
1: Speed search starts with last frequency
command
2: Starts with minimum output frequency

1

08.07

B.B. Time for Speed
Search

0.1 to 5.0 sec

0.5

08.08

Current Limit for
Speed Search

30 to 200%

150

08.09

Skip Frequency 1
Upper Limit

0.00 to 600.0 Hz

0.00

08.10

Skip Frequency 1
Lower Limit

0.00 to 600.0 Hz

0.00

08.11

Skip Frequency 2
Upper Limit

0.00 to 600.0 Hz

0.00

08.12

Skip Frequency 2
Lower Limit

0.00 to 600.0 Hz

0.00

08.13

Skip Frequency 3
Upper Limit

0.00 to 600.0 Hz

0.00

08.14

Skip Frequency 3
Lower Limit

0.00 to 600.0 Hz

0.00

08.15

Auto Restart After
Fault

0 to 10 (0=disable)

0

08.16

Auto Reset Time at
Restart after Fault

0.1 to 6000 sec

60.0

0: Disable

08.17

Auto Energy Saving 1: Enable

0