Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-19

Group 7 Motor Parameters

Parameter Explanation

Settings

Factory

Setting

Customer

07.00

Motor Rated Current
(Motor 0)

30 %FLA to 120% FLA

FLA

07.01

Motor No-Load
Current (Motor 0)

0%FLA to 99% FLA

0.4*FLA

07.02

Torque
Compensation
(Motor 0)

0.0 to 10.0

0.0

07.03 Slip

Compensation

(Used without PG)
(Motor 0)

0.00 to 10.00

0.00

07.04

Motor Parameters
Auto Tuning

0: Disable
1: Auto tuning R1
2: Auto tuning R1 + no-load test

0

07.05

Motor Line-to-line
Resistance R1
(Motor 0)

0~65535 m

Ω

0

07.06

Motor Rated Slip
(Motor 0)

0.00 to 20.00 Hz

3.00

07.07

Slip Compensation
Limit

0 to 250%

200

07.08

Torque
Compensation Time
Constant

0.01 ~10.00 Sec

0.10

07.09

Slip Compensation
Time Constant

0.05 ~10.00 sec

0.20

07.10

Accumulative Motor
Operation Time
(Min.)

0 to 1439 Min.

0

07.11

Accumulative Motor
Operation Time
(Day)

0 to 65535 Day

0

07.12

Motor PTC
Overheat Protection

0: Disable
1: Enable

0

07.13

Input Debouncing
Time of the PTC
Protection

0~9999(*2ms) 100