beautypg.com

Delta Electronics AC Motor Drive VFD-E User Manual

Page 82

background image

Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-29

Group 12: Analog Input/Output Parameters for Extension Card

Parameter Explanation

Settings

Factory

Setting

Customer

0: Disabled

1: Source of the 1st frequency

2: Source of the 2nd frequency

3: PID Set Point (PID enable)

4: Positive PID feedback

12.00

AI1 Function
Selection

5: Negative PID feedback

0

0: ACI2 analog current (0.0 ~ 20.0mA)

12.01

AI1 Analog Signal
Mode

1: AVI3 analog voltage (0.0 ~ 10.0V)

1

12.02

Min. AVI3 Input
Voltage

0.0 to 10.0V

0.0

12.03

Min. AVI3 Scale
Percentage

0.0 to 100.0%

0.0

12.04

Max. AVI3 Input
Voltage

0.0 to 10.0V

10.0

12.05

Max. AVI3 Scale
Percentage

0.0 to 100.0%

100.0

12.06

Min. ACI2 Input
Current

0.0 to 20.0mA

4.0

12.07

Min. ACI2 Scale
Percentage

0.0 to 100.0%

0.0

12.08

Max. ACI2 Input
Current

0.0 to 20.0mA

20.0

12.09

Max. ACI2 Scale
Percentage

0.0 to 100.0%

100.0

12.10

AI2 Function
Selection

0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
5: Negative PID feedback

0

0: ACI3 analog current (0.0 ~ 20.0mA)

12.11

AI2 Analog Signal
Mode

1: AVI4 analog voltage (0.0 ~ 10.0V)

1