Delta Electronics AC Motor Drive VFD-E User Manual
Page 82

Chapter 4 Parameters|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-29
Group 12: Analog Input/Output Parameters for Extension Card
Parameter Explanation
Settings
Factory
Setting
Customer
0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
12.00
AI1 Function
Selection
5: Negative PID feedback
0
0: ACI2 analog current (0.0 ~ 20.0mA)
12.01
AI1 Analog Signal
Mode
1: AVI3 analog voltage (0.0 ~ 10.0V)
1
12.02
Min. AVI3 Input
Voltage
0.0 to 10.0V
0.0
12.03
Min. AVI3 Scale
Percentage
0.0 to 100.0%
0.0
12.04
Max. AVI3 Input
Voltage
0.0 to 10.0V
10.0
12.05
Max. AVI3 Scale
Percentage
0.0 to 100.0%
100.0
12.06
Min. ACI2 Input
Current
0.0 to 20.0mA
4.0
12.07
Min. ACI2 Scale
Percentage
0.0 to 100.0%
0.0
12.08
Max. ACI2 Input
Current
0.0 to 20.0mA
20.0
12.09
Max. ACI2 Scale
Percentage
0.0 to 100.0%
100.0
12.10
AI2 Function
Selection
0: Disabled
1: Source of the 1st frequency
2: Source of the 2nd frequency
3: PID Set Point (PID enable)
4: Positive PID feedback
5: Negative PID feedback
0
0: ACI3 analog current (0.0 ~ 20.0mA)
12.11
AI2 Analog Signal
Mode
1: AVI4 analog voltage (0.0 ~ 10.0V)
1