Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-23

Parameter Explanation

Settings

Factory

Setting

Customer

0: AVR function enable

1: AVR function disable

2: AVR function disable for decel.

08.18 AVR

Function

3: AVR function disable for stop

0

115V / 230V series: 370.0to 430.0V

380.0

08.19

Software Brake
Level

460V series: 740.0 to 860.0V

760.0

08.20

Compensation
Coefficient for Motor
Instability

0.0~5.0

0.0

08.21

OOB Sampling Time 0.1 to 120.0 sec

1.0

08.22

Number of OOB
Sampling Times

00 to 32

20

08.23

OOB Average
Sampling Angle

Read only

#.#

08.24 DEB

Function

0: Disable
1: Enable

0

08.25

DEB Return Time

0 to 250 sec

0

Group 9 Communication Parameters

Parameter

Explanation

Settings

Factory

Setting

Customer

09.00

Communication
Address

1 to 254

1

0: Baud rate 4800bps

1: Baud rate 9600bps

2: Baud rate 19200bps

09.01 Transmission

Speed

3: Baud rate 38400bps

1

0: Warn and keep operating

1: Warn and ramp to stop

2: Warn and coast to stop

09.02

Transmission Fault
Treatment

3: No warning and keep operating

3