Chapter 4 Parameters|

4-66

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

1 0

Weights

Bit

Relay 1
MO1

3 2

5

4

7 6

MO2/RA2
MO3/RA3
MO4/RA4
MO5/RA5

MO6/RA6

MO7/RA7

0=not used

1=Used by PLC

For example: when Pr.03.09 is set to 3 (decimal) = 00000011 (binary) that indicates Relay1

and MO1 are used by PLC. (Pr.03.09= 2

0

+2

1

=3)

1 1

Weights

Bit

Relay 1
MO1

0 0

0

0

0 0

MO2/RA2
MO3/RA3
MO4/RA4
MO5/RA5

MO6/RA6

MO7/RA7

0=not used

1=Used by PLC

03.10

The Analog Output Used by PLC (NOT for VFD*E*C models)

Settings

Read Only

Factory setting: ##

Bit0=1: AFM used by PLC

Bit1=1: AO1 used by PLC

Bit2=1: AO2 used by PLC

The equivalent 1-bit is used to display the status (used or not used) of each analog output. The

value that Pr.03.10 displays is the result after converting 1-bit binary into decimal value.

0

Weights

Bit

0=not used

1=Used by PLC

AFM

1

2

AO1 (optional)
AO2 (optional)

For

Example:

If Pr.03.10 displays 1, it means that AFM is used by PLC.