beautypg.com

Master transmits data to slave pdo – Delta Electronics AC Motor Drive VFD-E User Manual

Page 357

background image

Appendix E CANopen Function |

E-8

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Type number 255 indicates the data is asynchronous transmission.

All PDO transmission data must be mapped to index via Object Dictionary.

Example:

Master transmits

data to Slave

PDO

PDO1

CAN(H)
CAN(L)

Master

Slave

PDO1 data value Data 0,

Data 1, Data 2, Data 3, Data 4, Data 5, Data 6, Data 7,

0x11, 0x22, 0x33, 0x44, 0x55, 0x66, 0x77, 0x88,

Index

Sub

Definition

Value

R/W

Size

1. Mapped Object

0. Number

2. Mapped Object
3. Mapped Object
4. Mapped Object

0
1
2
3
4

0x1600
0x1600
0x1600
0x1600
0x1600

R/W
R/W
R/W
R/W
R/W

1

0
0
0

U8

U32
U32
U32
U32

0x6040

0. Control word

0

R/W

U16

PDO1 Map

0x60400010

(2 Bytes)

0x60400010

0x2211

Slave returns message to Master

PDO1

CAN(H)
CAN(L)

Master

Slave

PDO1 data value Data 0,

Data 1, Data 2, Data 3, Data 4, Data 5, Data 6, Data 7,

0xF3, 0x00,

Index

Sub

Definition

Value

R/W

Size

1. Mapped Object

0. Number

2. Mapped Object
3. Mapped Object
4. Mapped Object

0
1
2
3
4

0x1A00
0x1A00
0x1A00
0x1A00
0x1A00

R/W
R/W
R/W
R/W
R/W

1

0
0
0

U8

U32
U32
U32
U32

0x6041

Status Word

0

R/W

U16

PDO1 Map

0x60410010

0xF3