Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-59

When Pr.02.07 is set to 1: increase/decrease the frequency by acceleration/deceleration

settings. It is valid only when the AC motor drive is running.

When Pr.02.07 is set to 2: increase/decrease the frequency by Pr.02.08.

When Pr.02.07 is set to 3: increase/decrease the frequency by Pr.02.08 (unit: pulse input).

02.11

Keypad Frequency Command

Unit: 0.01

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

This parameter can be used to set frequency command or read keypad frequency command.

02.12

Communication Frequency Command

Unit: 0.01

Settings

0.00 to 600.0Hz

Factory Setting: 60.00

This parameter can be used to set frequency command or read communication frequency

command.

02.13

The Selections for Saving Keypad or Communication Frequency
Command

Factory Setting: 0

Settings

0

Save Keypad & Communication Frequency

1

Save Keypad Frequency only

2

Save Communication Frequency only

This parameter is used to save keypad or RS-485 frequency command.

02.14

Initial Frequency Selection (for keypad & RS485/USB)

Factory Setting: 0

Settings

0

By Current Freq Command

1

By Zero Freq Command

2

By Frequency Display at Stop

02.15

Initial Frequency Setpoint (for keypad & RS485/USB)

Unit: 0.01

Settings

0.00 ~ 600.0Hz

Factory Setting: 60.00

These parameters are used to determinate the frequency at stop:

When setting Pr.02.14 to 0: the initial frequency will be current frequency.

When setting Pr.02.14 to 1: the initial frequency will be 0.

When setting Pr.02.14 to 2: the initial frequency will be Pr.02.15.