Chapter 4 Parameters|
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
4-129
09.06
Reserved
09.07
Response Delay Time
Unit: 2ms
Settings
0 ~ 200 (400msec)
Factory Setting: 1
This parameter is the response delay time after AC drive receives communication command
as shown in the following. 1 unit = 2 msec.
RS485 BUS
PC or PLC command
Handling time
of AC drive
Response Delay Time
Response Message of AC Drive
Max.: 6msec
Pr.09.07
09.08
Transmission Speed for USB Card
Factory Setting: 2
Settings
0
Baud rate 4800 bps
1
Baud rate 9600 bps
2
Baud rate 19200 bps
3
Baud rate 38400 bps
4
Baud rate 57600 bps
This parameter is used to set the transmission speed for USB card.