Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-129

09.06

Reserved

09.07

Response Delay Time

Unit: 2ms

Settings

0 ~ 200 (400msec)

Factory Setting: 1

This parameter is the response delay time after AC drive receives communication command

as shown in the following. 1 unit = 2 msec.

RS485 BUS

PC or PLC command

Handling time

of AC drive

Response Delay Time

Response Message of AC Drive

Max.: 6msec

Pr.09.07

09.08

Transmission Speed for USB Card

Factory Setting: 2

Settings

0

Baud rate 4800 bps

1

Baud rate 9600 bps

2

Baud rate 19200 bps

3

Baud rate 38400 bps

4

Baud rate 57600 bps

This parameter is used to set the transmission speed for USB card.

09.09

Communication Protocol for USB Card

Factory Setting: 1

Settings

0

Modbus

ASCII

mode, protocol <7,N,2>

1

Modbus ASCII mode, protocol <7,E,1>

2

Modbus ASCII mode, protocol <7,O,1>

3

Modbus RTU mode, protocol <8,N,2>

4

Modbus RTU mode, protocol <8,E,1>

5

Modbus RTU mode, protocol <8,O,1>

6

Modbus RTU mode, protocol <8,N,1>

7

Modbus RTU mode, protocol <8,E,2>

8

Modbus RTU mode, protocol <8,O,2>

9

Modbus ASCII mode, protocol <7,N,1>

10

Modbus ASCII mode, protocol <7,E,2>

11

Modbus ASCII mode, protocol <7,O,2>