beautypg.com

D.4 plc devices, D.4.1 summary of dvp-plc device number – Delta Electronics AC Motor Drive VFD-E User Manual

Page 302

background image

Appendix D How to Use PLC Function|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

D-19

D.4 PLC Devices

D.4.1 Summary of DVP-PLC Device Number

Items

Specifications

Remarks

Control Method

Stored program, cyclic scan
system

I/O Processing Method

Batch processing (when END
instruction is executed)

I/O refresh instruction is
available

Execution Speed

Basic commands (minimum
0.24 us)

Application commands
(10 ~ hundreds us)

Program Language

Instruction, Ladder Logic, SFC

Including the Step
commands

Program Capacity

500 STEPS

SRAM + Battery

Commands 45

commands

28 basic commands
17 application
commands

Input/Output Contact

Input (X): 6, output (Y): 2

X External Input Relay

X0~X17, 16 points,
octal number system

Correspond to external
input point

Y External Output Relay

Y0~Y17, 16 points,
octal number system

Total is

32

points Correspond to external

output point

For general

M0~M159, 160
points

M Auxiliary

For special

M1000~M1031, 32
points

Total is

192

points

Contacts can switch to
On/Off in program

T Timer 100ms timer

T0~T15, 16 points

Total is

16

points

When the timer
indicated by TMR
command attains the
setting, the T contact
with the same number
will be On.

16-bit count up for
general

C0~C7, 8 points

Total is

8 points

1-phase input

1-phase 2
inputs

Rela

y b

it

m

ode

C Counter

32-bit

count
up/down
high-
speed
counter

2-phase 2
inputs

C235, 1 point (need
to use with PG card)

Total is

1 point

When the counter
indicated by CNT
command attains the
setting, the C contact
with the same number
will be On.