Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-91

06.01

Over-Current Stall Prevention during Acceleration

Unit: 1

Settings

20 to 250%

Factory Setting: 170

0:

disable

A setting of 100% is equal to the Rated Output Current of the drive.

During acceleration, the AC drive output current may increase abruptly and exceed the value

specified by Pr.06.01 due to rapid acceleration or excessive load on the motor. When this

function is enabled, the AC drive will stop accelerating and keep the output frequency constant

until the current drops below the maximum value.

06.01

Over-Current

Detection
Level

Output

Frequency

Over-Current Stall

prevention during
Acceleration,

frequency held

output current

time

setting
frequency

previous acceleration time

actual acceleration time when over-current stall

prevention is enabled

06.02

Over-current Stall Prevention during Operation

Unit: 1

Settings

20 to 250%

Factory Setting: 170

0:

disable

If the output current exceeds the setting specified in Pr.06.02 when the drive is operating, the

drive will decrease its output frequency to prevent the motor stall. If the output current is lower

than the setting specified in Pr.06.02, the drive will accelerate again to catch up with the set

frequency command value.