beautypg.com

Delta Electronics AC Motor Drive VFD-E User Manual

Page 124

background image

Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-71

Example 5: Use of negative bias in noisy environment

In this example, a 1V negative bias is used. In noisy environments it is advantageous to use negative

bias to provide a noise margin (1V in this example).

60Hz

0Hz

0V

10V

Pr.01.00=60Hz--Max. output Freq.

Potentiometer

Pr.04.00 =10.0%--Bias adjustment

Pr.04.01 =1--Negative bias
Pr.04.02 =100%--Input gain

Pr.04.03 =0--No negative bias command

Gain:100%

Bias adjustment:((6Hz/60Hz)/(Gain/100%))*100%=10.0%

Negative
bias 6Hz

1V

54Hz

Example 6: Use of negative bias in noisy environment and gain adjustment to use full

potentiometer range

In this example, a negative bias is used to provide a noise margin. Also a potentiometer frequency

gain is used to allow the Maximum Output Frequency to be reached.

60Hz

0Hz

0V

10V

Pr.01.00=60Hz--Max. output Freq.

Negative
bias 6.6Hz

1V

Bias
adjustment

Potentiometer

Pr.04.00 =10.0%--Bias adjustment
Pr.04.01 =1--Negative bias

Pr.04.02 =111%--Input gain
Pr.04.03 =0--No negative bias command

Gain:(10V/9V)*100%=111%

Bias adjustment:((6.6Hz/60Hz)/(Gain/100%))*100%=10.0%

Example 7: Use of 0-10V potentiometer signal to run motor in FWD and REV direction

In this example, the input is programmed to run a motor in both forward and reverse direction. The

motor will be idle when the potentiometer position is at mid-point of its scale. Using the settings in this

example disables the external FWD and REV controls.