Parameter Explanation

Settings

Factory

Setting

Customer

07.14

Motor PTC
Overheat Protection
Level

0.1~10.0V 2.4

07.15

Motor PTC
Overheat Warning
Level

0.1~10.0V 1.2

07.16

Motor PTC
Overheat Reset
Delta Level

0.1~5.0V 0.6

07.17

Treatment of the
Motor PTC
Overheat

0: Warn and RAMP to stop
1: Warn and COAST to stop
2: Warn and keep running

0

07.18

Motor Rated Current
(Motor 1)

30 %FLA to 120% FLA

FLA

07.19

Motor No-Load
Current (Motor 1)

0%FLA to 99% FLA

0.4*FLA

07.20

Torque
Compensation
(Motor 1)

0.0 to 10.0

0.0

07.21

Slip Compensation
(Used without PG)
(Motor 1)

0.00 to 10.00

0.00

07.22

Motor Line-to-line
Resistance R1
(Motor 1)

0~65535 m

Ω

0

07.23

Motor Rated Slip
(Motor 1)

0.00 to 20.00 Hz

3.00

07.24

Motor Pole Number
(Motor 1)

2 to 10

4

07.25

Motor Rated Current
(Motor 2)

30 %FLA to 120% FLA

FLA

07.26

Motor No-Load
Current (Motor 2)

0%FLA to 99% FLA

0.4*FLA

07.27

Torque
Compensation
(Motor 2)

0.0 to 10.0

0.0

07.28

Slip Compensation
(Used without PG)
(Motor 2)

0.00 to 10.00

0.00