Delta Electronics AC Motor Drive VFD-E User Manual

Page 91

background image

Chapter 4 Parameters|

4-38

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

This parameter allows the user to reset all parameters to the factory settings except the fault

records (Pr.06.08 ~ Pr.06.12).

50Hz: Pr.01.00 and Pr.01.01 are set to 50Hz and Pr.01.02 will be set by Pr.00.12.

60Hz: Pr.01.00 and Pr.01.01 are set to 60Hz and Pr.01.02 is set to 115V, 230V or 460V.

When Pr.00.02=1, all parameters are read-only. To write all parameters, set Pr.00.02=0.

00.03

Start-up Display Selection

Factory Setting: 0

Settings 0

Display the frequency command value (Fxxx)

1

Display the actual output frequency (Hxxx)

2

Display the output current in A supplied to the motor
(Axxx)

3

Display the content of user-defined unit (Uxxx)

4

FWD/REV

command

5

PLCx (PLC selections: PLC0/PLC1/PLC2)
(NOT for VFD*E*C models)

This parameter determines the start-up display page after power is applied to the drive.

For setting 5, PLC0: disable, PLC1: run PLC, PLC2: read/write PLC programs into AC motor

drive.

00.04

Content of Multi-function Display

Factory Setting: 0

Settings 0

Display the content of user-defined unit (Uxxx)

1

Display the counter value which counts the number of

pulses on TRG terminal

2

Display PLC D1043 value (C)
(NOT for VFD*E*C models)

3

Display the actual DC BUS voltage in VDC of the AC
motor drive

4

Display the output voltage in VAC of terminals U/T1,
V/T2, W/T3 to the motor.

5

Display PID analog feedback signal value in %