Chapter 4 Parameters|
4-124
Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11
Content Address
Function
2001H
Frequency command
Bit 0
1: EF (external fault) on
Bit 1
1: Reset
2002H
Bit 2-15
Reserved
Error code:
0: No error occurred
Status
monitor
Read only
2100H
1: Over-current (oc)
2:
Over-voltage
(ov)
3: IGBT Overheat (oH1)
4: Power Board Overheat (oH2)
5:
Overload
(oL)
6:
Overload1
(oL1)
7:
Overload2
(oL2)
8: External fault (EF)
9: Current exceeds 2 times rated current during accel (ocA)
10: Current exceeds 2 times rated current during decel (ocd)
Current exceeds 2 times rated current during decel (ocd)
11: Current exceeds 2 times rated current during steady state
operation (ocn)
12: Ground Fault (GFF)
13: Low voltage (Lv)
14:
PHL
(Phase-Loss)
2100H
15: Base Block
16: Auto accel/decel failure (cFA)
17: Software protection enabled (codE)
18: Power Board CPU WRITE failure (CF1.0)
19: Power Board CPU READ failure (CF2.0)
20: CC, OC Hardware protection failure (HPF1)
21: OV Hardware protection failure (HPF2)
22: GFF Hardware protection failure (HPF3)
23: OC Hardware protection failure (HPF4)