beautypg.com

4 low voltage (lv), 4 low voltage (lv) -3 – Delta Electronics AC Motor Drive VFD-E User Manual

Page 214

background image

Chapter 5 Troubleshooting|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

5-3

5.4 Low Voltage (Lv)

Low voltage

Is input power correct? Or power cut,
including momentary power loss

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

Restart after reset

Check if there is any malfunction
component in

power supply circuit

or disconnection

Change defective component

and check connection

Check if voltage is

within specification

Make necessary corrections,

such as change power supply

system for requirement

Check if there is heavy load

with high start current in the

same power system

Check if Lv occurs when
breaker and magnetic

contactor is ON

Suitable

transformer

power

capacity

Check if voltage between +/B1

and - is greater than
200VDC (for 115V/230V models)

400VDC (for 460V models)

Maybe AC motor drive has malfunction.

Please contact DELTA.

Control circuit has malfunction or

misoperation due to noise. Please

contact DELTA.

Yes

Using the different power

supply for this drive and
heavy load system