Chapter 4 Parameters|

4-8

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

Parameter Explanation

Settings

Factory

Setting

Customer

2: Disable. Operation status will change if
operation command source Pr.02.01 is
changed.

3: Enable. Operation status will change if
operation command source Pr.02.01 is
changed.

0: Decelerate to 0 Hz

1: Coast to stop and display “AErr”

02.06

Loss of ACI Signal
(4-20mA)

2: Continue operation by last frequency
command

1

0: by UP/DOWN Key

1: Based on accel/decel time

2: Constant speed (Pr.02.08)

02.07

Up/Down Mode

3: Pulse input unit (Pr.02.08)

0

02.08

Accel/Decel Rate of
Change of
UP/DOWN
Operation with
Constant Speed

0.01~10.00 Hz

0.01

02.09

Source of Second
Frequency
Command

0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI or 0 to +10V from
AVI2
3: RS-485 (RJ-45)/USB communication
4: Digital keypad potentiometer
5: CANopen communication

0

02.10

Combination of the
First and Second
Master Frequency
Command

0: First Master Frequency Command
1: First Master Frequency Command+
Second Master Frequency Command
2: First Master Frequency Command -
Second Master Frequency Command

0

02.11

Keypad Frequency
Command

0.00 to 600.0Hz

60.00

02.12

Communication
Frequency
Command

0.00 to 600.0Hz

60.00