Chapter 4 Parameters|

4-58

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

02.06

Loss of ACI Signal (4-20mA)

Factory Setting: 0

Settings

0

Decelerate

to

0Hz

1

Coast to stop and display “AErr”

2

Continue operation by the last frequency command

This parameter determines the behavior when ACI is lost.

When set to 1, it will display warning message “AErr” on the keypad in case of loss of ACI

signal and execute the setting. When ACI signal is recovered, the warning message will stop

blinking. Please press “RESET” key to clear it.

02.07

Up/Down Mode

Factory Setting: 0

Settings

0

By digital keypad up/down keys mode

1

Based on Accel/Decel Time acc. to Pr.01.09 to 01.12

2

Constant speed (acc. to Pr. 02.08)

3

Pulse input unit (acc. to Pr. 02.08)

02.08

Accel/Decel Rate of Change of UP/DOWN Operation with
Constant Speed

Unit: 0.01

Settings

0.01~10.00 Hz/2ms

Factory Setting: 0.01

These parameters determine the increase/decrease of the master frequency when operated

via the Multi-function Inputs when Pr.04.05~Pr.04.08 are set to 10 (Up command) or 11 (Down

command).

When Pr.02.07 is set to 0: increase/decrease the frequency by using UP/DOWN key. It is valid

only when the AC motor drive is running.

0

9.0Hz

50.0Hz

600Hz

4.34 s

3.28 s

3.68 s

t (sec)