Chapter 4 Parameters|

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

4-113

09.03

Time-out Detection

Unit: 0.1

Settings

0.0 to 120.0 sec

Factory Setting: 0.0

0.0

Disable

If Pr.09.03 is not equal to 0.0, Pr.09.02=0~2, and there is no communication on the bus during

the Time Out detection period (set by Pr.09.03), “cE10” will be shown on the keypad.

09.04

Communication Protocol

Factory Setting: 0

Settings

0

Modbus

ASCII

mode, protocol <7,N,2>

1

Modbus ASCII mode, protocol <7,E,1>

2

Modbus ASCII mode, protocol <7,O,1>

3

Modbus RTU mode, protocol <8,N,2>

4

Modbus RTU mode, protocol <8,E,1>

5

Modbus RTU mode, protocol <8,O,1>

6

Modbus RTU mode, protocol <8,N,1>

7

Modbus RTU mode, protocol <8,E,2>

8

Modbus RTU mode, protocol <8,O,2>

9

Modbus ASCII mode, protocol <7,N,1>

10

Modbus ASCII mode, protocol <7,E,2>

11

Modbus ASCII mode, protocol <7,O,2>

1. Control by PC or PLC



A VFD-E can be set up to communicate in Modbus networks using one of the following

modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote

Terminal Unit). Users can select the desired mode along with the serial port

communication protocol in Pr.09.04.



Code Description:

The CPU will be about 1 second delay when using communication reset. Therefore, there

is at least 1 second delay time in master station.

ASCII mode:

Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data:

64 Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).

Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’

ASCII code

30H

31H

32H

33H

34H

35H

36H

37H