D.4.6 The Features and Functions of Counter

Features:

Item

16 bits counters

32 bits counters

Type General

General

High

speed

Count direction

Count up

Count up/down

Settings 0~32,767

-2,147,483,648~+2,147,483,647

Designate for
constant

Constant K or data register D Constant K or data register D (2 for designated)

Present value
change

Counter will stop when
attaining settings

Counter will keep on counting when attaining
settings

Output contact

When count attains settings,
contact will be On and
latched.

When count up attains settings, contact will be On
and latched.
When count down attains settings, contact will
reset to Off.

Reset action

The present value will reset to 0 when RST command is executed and contact
will reset to Off.

Present register

16 bits

32 bits

Contact action

After scanning, act together.

After scanning,
act together.

Act immediately when count
attains. It has no relation with
scan period.

Functions:

When pulse input signal of counter is from Off to On, the present value of counter equals to settings

and output coil is On. Settings are decimal system and data register D can also be used as settings.

16-bit counters C0~C7:

1.

Setting range of 16-bit counter is K0~K32,767. (K0 is the same as K1. output contact will

be On immediately at the first count.

2.

General counter will be clear when PLC is power loss. If counter is latched, it will

remember the value before power loss and keep on counting when power on after power

loss.

3.

If using MOV command, WPLSoft to send a value, which is large than setting to C0,

register, at the next time that X1 is from Off to On, C0 counter contact will be On and

present value will be set to the same as settings.

4.

The setting of counter can use constant K or register D (not includes special data register

D1000~D1044) to be indirect setting.

5.

If using constant K to be setting, it can only be positive number but if setting is data

register D, it can be positive/negative number. The next number that counter counts up

from 32,767 is -32,768.