Chapter 4 Parameters|

4-56

Revision June 2008, 04EE, SW--PW V1.11/CTL V2.11

02.05

Line Start Lockout

Factory Setting: 1

Settings

0

Disable. Operation status is not changed even if operation
command source Pr.02.01 is changed.

1

Enable. Operation status is not changed even if operation command
source Pr.02.01 is changed.

2

Disable. Operation status will change if operation command source
Pr.02.01 is changed.

3

Enable. Operation status will change if operation command source
Pr.02.01 is changed.

This parameter determines the response of the drive upon power on and operation command

source is changed.

Pr.02.05

Start lockout (Run when power is ON)

Operation status when operation

command source is changed

0

Disable (AC motor drive will run)

Keep previous status

1

Enable (AC motor drive doesn’t run)

Keep previous status

2

Disable (AC motor drive will run)

Change according to the new

operation command source

3

Enable (AC motor drive doesn’t run)

Change according to the new

operation command source

When the operation command source is from external terminal and operation command is ON

(MI1/MI2-DCM=closed), the AC motor drive will operate according to Pr.02.05 after power is

applied.

1. When Pr.02.05 is set to 0 or 2, AC motor drive will run immediately.

2. When Pr.02.05 is set to 1 or 3, AC motor drive will remain stopped until operation

command is received after previous operation command is cancelled.